Power line protection zone
Electricity

Power line protection zone: how many metres by voltage

Rusya

Exact statutory table (Decree No. 160): from 2 m (<1 kV) to 30 m (330–500 kV), cable 1 m.

Mesafeler ve kurallar

The protection zone of an overhead power line is measured from the outer conductors on each side and grows with voltage. Inside it, building and many works need the grid operator’s consent.

Up to 1 kV 2 m on each side RF Government Decree No. 160 (24.02.2009)
6–20 kV 10 m on each side RF Government Decree No. 160 (24.02.2009)
150–220 kV 25 m on each side RF Government Decree No. 160 (24.02.2009)
330–500 kV 30 m on each side RF Government Decree No. 160 (24.02.2009)
Underground cable 1 m on each side RF Government Decree No. 160 (24.02.2009)
Forbidden inside Building, storage, planting/felling trees, open fire, earthworks and blasting — without the grid operator’s written consent. RF Government Decree No. 160 (24.02.2009)
Allowed Passage, driving across and mowing grass. Yerel kurallar

Önemli kısıtlama

Bu bir planlama yardımcısıdır, yasal bir görüş değildir. İnşaattan önce yerel arazi kullanım kurallarını, irtifak haklarını, şebeke/altyapı operatörünün gereksinimlerini ve komşu binaları kontrol edin.