Power line protection zone
Electricity

Power line protection zone: how many metres by voltage

Russland

Exact statutory table (Decree No. 160): from 2 m (<1 kV) to 30 m (330–500 kV), cable 1 m.

Abstände und Regeln

The protection zone of an overhead power line is measured from the outer conductors on each side and grows with voltage. Inside it, building and many works need the grid operator’s consent.

Up to 1 kV 2 m on each side RF Government Decree No. 160 (24.02.2009)
6–20 kV 10 m on each side RF Government Decree No. 160 (24.02.2009)
150–220 kV 25 m on each side RF Government Decree No. 160 (24.02.2009)
330–500 kV 30 m on each side RF Government Decree No. 160 (24.02.2009)
Underground cable 1 m on each side RF Government Decree No. 160 (24.02.2009)
Forbidden inside Building, storage, planting/felling trees, open fire, earthworks and blasting — without the grid operator’s written consent. RF Government Decree No. 160 (24.02.2009)
Allowed Passage, driving across and mowing grass. Lokale Regeln

Wichtige Einschränkung

Dies ist eine Planungshilfe, keine Rechtsberatung. Prüfen Sie vor dem Bau die örtlichen Flächennutzungsregeln, Dienstbarkeiten, die Anforderungen des Netz-/Versorgungsbetreibers sowie benachbarte Gebäude.