Electricity
Power line protection zone: how many metres by voltage
Russland
Exact statutory table (Decree No. 160): from 2 m (<1 kV) to 30 m (330–500 kV), cable 1 m.
Abstände und Regeln
The protection zone of an overhead power line is measured from the outer conductors on each side and grows with voltage. Inside it, building and many works need the grid operator’s consent.
Up to 1 kV
2 m on each side
RF Government Decree No. 160 (24.02.2009)
6–20 kV
10 m on each side
RF Government Decree No. 160 (24.02.2009)
35 kV
15 m on each side
RF Government Decree No. 160 (24.02.2009)
110 kV
20 m on each side
RF Government Decree No. 160 (24.02.2009)
150–220 kV
25 m on each side
RF Government Decree No. 160 (24.02.2009)
330–500 kV
30 m on each side
RF Government Decree No. 160 (24.02.2009)
Underground cable
1 m on each side
RF Government Decree No. 160 (24.02.2009)
Forbidden inside
Building, storage, planting/felling trees, open fire, earthworks and blasting — without the grid operator’s written consent.
RF Government Decree No. 160 (24.02.2009)
Allowed
Passage, driving across and mowing grass.
Lokale Regeln
Wichtige Einschränkung
Dies ist eine Planungshilfe, keine Rechtsberatung. Prüfen Sie vor dem Bau die örtlichen Flächennutzungsregeln, Dienstbarkeiten, die Anforderungen des Netz-/Versorgungsbetreibers sowie benachbarte Gebäude.