Electricity
Power line protection zone: how many metres by voltage
Frankreich
Servitude I4 sets building-restriction perimeters per line; values are planning guidance.
Abstände und Regeln
The protection zone of an overhead power line is measured from the outer conductors on each side and grows with voltage. Inside it, building and many works need the grid operator’s consent.
Up to 1 kV
1.5 m on each side
Lokale Regeln
6–20 kV
7 m on each side
Lokale Regeln
35 kV
10 m on each side
Lokale Regeln
110 kV
14 m on each side
Lokale Regeln
150–220 kV
22 m on each side
Lokale Regeln
330–500 kV
35 m on each side
Lokale Regeln
Underground cable
1.5 m on each side
Lokale Regeln
Forbidden inside
Building, storage, planting/felling trees, open fire, earthworks and blasting — without the grid operator’s written consent.
Lokale Regeln
Allowed
Passage, driving across and mowing grass.
Lokale Regeln
Wichtige Einschränkung
Dies ist eine Planungshilfe, keine Rechtsberatung. Prüfen Sie vor dem Bau die örtlichen Flächennutzungsregeln, Dienstbarkeiten, die Anforderungen des Netz-/Versorgungsbetreibers sowie benachbarte Gebäude.